PUE math — and what it hides
PUE = total facility energy ÷ IT energy: 100 kW of IT with 15 kW of overhead scores 1.15. Liquid cooling reaches 1.05-1.2 where air needs 1.4-1.6 — but the number assumes facility-scale infrastructure and honest climate, which single-cabinet deployments don't have.
Formula
Worked example
A facility moving 100 kW of IT heat with 10 kW of cooling energy (efficient free-cooling or liquid), 4 kW of UPS/conversion losses and 1 kW of lighting and controls runs at PUE 1.15. The same site on legacy air with 45 kW of cooling energy runs 1.50.
Try it
What it hides
- Climate is invisible. The same hardware scores differently in Munich and Singapore — free cooling hours depend on wet-bulb (wet-bulb physics). Cross-climate PUE comparisons are marketing, not engineering.
- Liquid cooling doesn't shrink IT power. It shrinks the cooling term. A rack's IT draw is the same; what changes is how cheaply the heat leaves the building.
- A cabinet in a room has no honest PUE. If the "facility" is office AC shared with humans, the boundary is undefined. Use the 1.1× room load rule instead for micro deployments.
Related
Room AC load · Wet-bulb & free cooling · Liquid vs air
Sources
Definition: The Green Grid / ISO/IEC 30134-2. Band context: Uptime Institute global surveys (air-cooled averages ≈ 1.5; leading liquid-cooled facilities 1.1 or below).