Select a real cooling product and real server platforms, set the room, and watch capacity derate against it. Server watts are TDP budgets (ΣGPU + ΣCPU) × 1.2 from public specs — every selection links its source. Same physics as the formulas section.

Cooling product

No facility water — but the room must absorb ~1.1× IT load in AC · source ↗

Servers

42U RACK · 32U USED
8× H100 SXM node (HGX H100/H200) ×4 · 7.6 kW
8× H100 SXM node (HGX H100/H200): 8× H100/H200 SXM (700 W) + 2× CPU (360 W) — spec ↗

Readouts

LIQUID LOAD vs DERATED CAPACITY
24.3 kW / 86.5 kW (28%)
RACK SPACE
32U / 42U
ROOM

Capacity derates with room air (why)

✅ Fits — 72% thermal headroom, 10U free, at 25 °C
Total IT30.4 kWHeat to liquid24.3 kW
Heat to air6.1 kWCoolant flow @ ΔT 8 °C44 L/min
Capacity at 25 °C room86.5 kWRoom AC (1.1×)33.4 kW ≈ 9.5 tons
FIG. 1 — Live build. Flow: L/min = kW × 60 / (4.186 × ΔT). Derating: approach-temperature model on the selected product's rating point. Watts are TDP budgets, not measured draw.

Try this

  • Add one GB200 NVL72 rack with the 30 kW cabinet selected → the gap is the whole story: no single-cabinet class fits a 120 kW rack.
  • 8× H100 × 4 nodes + Vertiv CDU 70 → fits at 25 °C; slide the room to 35 °C and watch the verdict flip.
  • Switch to Asetek L2L → capacity stops derating, but the facility-water requirement takes over the room-AC line.