ASHRAE W-classes (W17–W45)
ASHRAE sorts liquid-cooled equipment into coolant supply temperature classes: W17, W27, W32, W40, W45 — the number is the maximum facility water supply temperature in °C. Higher classes reject heat into warmer water, enabling chiller-free operation — if the IT hardware supports it.
The table
| Class | Max facility supply | What it implies for the site |
|---|---|---|
| W17 | ≈ 17 °C | Chilled water required — compressors run year-round; historic baseline |
| W27 | ≈ 27 °C | Cooler climate or partial free cooling; chiller mostly shoulder-season |
| W32 | ≈ 32 °C | Most temperate sites' free-cooling target; dry coolers viable much of the year |
| W40 | ≈ 40 °C | Chiller-less operation in most of Europe/North America via dry coolers |
| W45 | ≈ 45 °C | Warm-water direct-to-chip; the class behind "free cooling almost everywhere" claims — and the rating point of typical L2A cabinets |
Look up your site
Needs class ≥ 32
W32: the common free-cooling target — dry coolers cover much of the year in temperate sites
Reading it honestly
- W-class is about the facility loop, not the room. Room air classes (A1-A4) are a separate ladder for air-cooled IT; do not mix them in a quote.
- Warmer water trades chiller hours for chip margin. A W45 loop lets the site skip refrigeration, but every degree of warmer coolant raises cold-plate approach and chip temperatures — capacity and silicon limits pay for the efficiency.
- Temperature is only half the spec. Classes assume water quality targets (corrosion, biology, particulates); PG25 with inhibitors is the usual answer on the technology loop (fluids).
- Tropics cap the ladder. With design wet-bulbs near 28-30 °C, even W45 loops lose dry-cooler margin — the physics behind wet-bulb limits and SS 726.