Pressure drop (Darcy–Weisbach)
Every meter of hose and every coupling eats pump head: 90 L/min through 25 mm hose loses ≈ 20 kPa over 3 m (f = 0.035). If the loop's total drop exceeds the CDU's available head, flow falls below the formula on paper — and the rack overheats on a Friday afternoon.
Formula
Darcy–Weisbach with friction factor f (≈ 0.03-0.04 for smooth hose at these flows), ρ ≈ 1,020 kg/m³ for PG25, and v the flow velocity. Velocity is the killer — it enters squared, which is why stepping down one hose size hurts so much.
Worked example
That is just one straight hose. Add the rack manifold, two UQD couplings, elbows and the CDU heat exchanger, and a loop can easily demand 100-150 kPa — which is exactly what CDU pump curves are sized against.
Try it
Common mistakes
- Undersized hose. Halving diameter multiplies velocity fourfold and drop roughly sixteen-fold (v² and D both bite). 25 mm+ supply lines are normal at rack flows for a reason.
- Ignoring fittings and the UQD. Each elbow adds an equivalent length; a quick disconnect is often the single highest-drop element in a sub-loop. Count them, don't wish them away.
- Reading the pump curve wrong. A CDU's "available head" is at a flow rate; as loop drop rises, operating flow slides down the curve. Check the intersection, not the brochure peak.
Related
Coolant flow rate (what Q should be) · What is a CDU? · Commissioning (verifying real ΔP and flow)
Sources
Darcy–Weisbach with Darcy friction factor; PG25 density ≈ 1,020 kg/m³ at 25 °C. Friction factor from Moody/Colebrook smooth-pipe turbulence — engineering approximation for first-pass sizing, not a substitute for vendor loop data.