Formula · 3 min read
Approach temperature & derating
Approach temperature is the gap between coolant supply and room air temperature: approach = Tcoolant − Tair. Liquid-to-air capacity scales roughly linearly with it — which is why a cabinet rated 86.5 kW at 45 °C coolant / 25 °C air (Vertiv XDU070) delivers about half at 35 °C air.
Formula
A heat exchanger transfers heat in proportion to the temperature difference across it. When room air warms from 25 °C to 35 °C, the approach on a 45 °C coolant loop falls from 20 °C to 10 °C and capacity halves. Below roughly 5 °C of approach, the exchanger can no longer move meaningful heat — capacity collapses. This is the first-principles reason hot climates derate everything.
Worked example
Try it
Common mistakes
- Comparing nameplate to a tropical room. Nameplate capacity is quoted at 25 °C air / 45 °C coolant. At 35 °C ambient you get roughly half; buy the derated number, not the brochure number.
- Chasing capacity by lowering coolant temperature. Below the room's dew point, supply lines and cold plates condense water onto live electronics. This is exactly what ASHRAE W-classes exist to prevent — coolant temperature is a floor, not a free lever.
- Forgetting the model is linear. Real capacity curves bow (fan power, flow limits); always get the vendor's capacity-vs-ambient table. The linear model here is the honest first pass — Vertiv is one of the few publishers of real curves (XDU070).