Interactive · three inputs, live math, honest verdict
Room load calculator
Can your room host a liquid-to-air cabinet? The formula shows itself with your numbers — and the bar shows how thin the margin really is.
⚠️ Conditional — derate the cabinet or verify AC condition
| Heat to reject | 1.1 × 30 = 33.0 kW |
| …in refrigeration tons | 33.0 ÷ 3.517 = 9.4 tons |
| AC spare capacity | 35 − 0 = 35.0 kW |
| Margin | 35.0 ÷ 33.0 = 1.06× |
Try this
- IT 30 kW, AC 35 kW, existing 0 → green, but the bar shows the margin is one hot afternoon wide.
- Add 5 kW of existing equipment in the same zone → green turns red. Zones matter.
- Keep the AC, halve the IT load → find the load this room can actually host.
Rule: margin ≥ 1.15 green · 1.0–1.15 conditional · < 1.0 insufficient. The 1.1 factor covers pumps and fans — the 1.1× rule explained · full worked guide in room load calculation.